4.2 Single-Host Installation of an SF3xx Storage Array
Figure 4–7 Placing a Label on the OCP Door
Write
Protect
Ready Fault
DSSI
ID
Write
Protect
Ready Fault
DSSI
ID
d
i g i
t
a l
SHR_X1128C_89
1
2
NNnNN
4.2.4 Powering Up the SF3xx Storage Array (Single-Host)
Now that the SF3xx storage array has been installed and labeled, you are
ready to apply power. Follow the steps in order.
CAUTION
Make sure that the ac power switch on each SF7x storage enclosure
and magazine tape subsystem installed is in the off position.
1. At the rear of the storage array, turn the power controller on. Make sure
that the BUS/OFF/ON switch is in the down position.
2. At the rear of the storage array, turn on each magazine tape subsystem
installed (if present). Observe the front panel. If a failure occurs, see
Chapter 8.
3. At the rear of the storage array, turn on each SF7x storage enclosure
starting with position 1 and continuing in numerical order.
4–12 Installing an SF3xx Storage Array to a VAX 6000 System